Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM05287
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
02/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/24/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
03/10/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Provide connection details to show connections at the frame haunches and at the ridge. 2) How are the diagonal braces connected at the roof and the elevations shown. Show the connection detail. 3) Provide connection details of lintels, girts to columns and other structural members. 4) How is metal sheathing attached to structural members? 5) In all connection details specify the size, type and number of connectors for the a particular connection. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/15/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
03/15/2005 | SUE REEVES | REJECT SHELF | Completed |