Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2004 PATRICIA GEHLEN ZONING REVIEW Approved
05/11/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approv-Cond
05/21/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Load calculations list new Panel C load as 46 A. According to the tabulation on the Panel Schedule, this figure is 60A in aggregate, and 62 A high phase. Please correct.
2. Please verify that clamp-on ammeter test for existing loads were performed with power on to all devices. Otherwise, another method will have to used to determine existing load.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2004 DELMA ROBEY OUT TO CUSTOMER Completed