Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2003 EROSE1 WWM REVIEW Needs Review
11/26/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Provide architectural detail for refrigerant penetrations through roof as referenced on Sheet M2.

PLUMBING COMMENTS
Sheet P1
1. Coordinate fixture demolition and relocation with Pima County Wastewater Management for additional assistance call 740-6500. Advisory comment only. No response required.

MECHANICAL COMMENTS
General
1. Coordinate smoke detection systems control with the electrical drawings. Ref. IMC 606.


Sheet M2
1. The note on this sheet references the architectural drawings for refrigerant line roof penetrations. This detail is not found in the architectural drawings. Please coordinate this construction detail as noted.

ELECTRICAL COMMENTS
General
1. Coordinate smoke detection systems control. Ref. IMC 606.

Sheet E1
1. Circuit "BA" 20 is used twice. Clarify.

2. Circuits "BA" 8 and "BA" 24 shown as lighting in the panel schedule, do not appear to have been used. Please clarify.

Sheet E2
1. Circuits 31 and 33 on panel BA are shown on the plan as power to rooms 113, 118 and 119. The panel schedule identifies these circuits as spares. Please revise.

2. Power for room 116 appears to be served by "BA #15" but has not been shown on the plan. Please clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved
11/26/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2003 ELAINE ROSE OUT TO CUSTOMER Completed