Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sink in multi-function room is called out as a kitchen sink (5 places) and as a bar sink (1 place). Since it is associated with a dishwasher, consider it a kitchen sink rated at 4 water fixture units and 3 waste fixture units.
2. The provided calculations indicate that a 1/2" water line can handle no more than 3 fixture units. Revise pipe sizes as required.
3. Provide sealed drawings.
11/18/2003 GERRY KOZIOL WWM REVIEW Denied Needs addressing review. 2 - suite #100
11/25/2003 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/25/2003 LLESNY1 ZONING REVIEW Needs Review
11/25/2003 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review