Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM05275
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05275
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sink in multi-function room is called out as a kitchen sink (5 places) and as a bar sink (1 place). Since it is associated with a dishwasher, consider it a kitchen sink rated at 4 water fixture units and 3 waste fixture units.
2. The provided calculations indicate that a 1/2" water line can handle no more than 3 fixture units. Revise pipe sizes as required.
3. Provide sealed drawings.
11/18/2003 GERRY KOZIOL WWM REVIEW Denied Needs addressing review. 2 - suite #100
11/25/2003 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/25/2003 LLESNY1 ZONING REVIEW Needs Review
11/25/2003 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2003 LISA LESNY OUT TO CUSTOMER Completed