11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sink in multi-function room is called out as a kitchen sink (5 places) and as a bar sink (1 place). Since it is associated with a dishwasher, consider it a kitchen sink rated at 4 water fixture units and 3 waste fixture units.
2. The provided calculations indicate that a 1/2" water line can handle no more than 3 fixture units. Revise pipe sizes as required.
3. Provide sealed drawings.