Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05275
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05275
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2003 TACHONG1 ZONING REVIEW Needs Review
11/12/2003 GERRY KOZIOL WWM REVIEW Needs Review
11/12/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
11/12/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied Bob Suba - Electrical Review Comments 11/10/03
1) Properly calculate CIR's B-9, B-1
2) H.P.7 should be either protected at 30 amps (B37,39,41) at panel "B" or increase conductor size to #8
3) Clarify what the available fault current is - provide equip. calculations
4) Indicate panel location on electrical plan
5) Indicate grounding conductor and size in existing 2-1/2" conduit.
11/12/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
11/12/2003 TAMI ACHONG OUT TO CUSTOMER Completed