Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/12/2003 | TACHONG1 | ZONING | REVIEW | Needs Review | |
11/12/2003 | GERRY KOZIOL | WWM | REVIEW | Needs Review | |
11/12/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
11/12/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Bob Suba - Electrical Review Comments 11/10/03 1) Properly calculate CIR's B-9, B-1 2) H.P.7 should be either protected at 30 amps (B37,39,41) at panel "B" or increase conductor size to #8 3) Clarify what the available fault current is - provide equip. calculations 4) Indicate panel location on electrical plan 5) Indicate grounding conductor and size in existing 2-1/2" conduit. |
11/12/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/12/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |