Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05275
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05275
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2003 JIM EGAN FIRE REVIEW Approved
11/06/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The maximum length for a 1-1/2" trap arm is 3'-6". Reference Section 1002.2, UPC 1994.
2. Provide calculations to show that the water piping has been sized per Section 610, UPC 1994.
3. Include the total building water demand in the water calculations to show that this TI does not overload the existing piping. Reference Section 101.5.1, UPC 1994.
11/06/2003 MVALDEZ1 ZONING REVIEW Needs Review
11/06/2003 MVALDEZ1 WWM REVIEW Needs Review
11/06/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/06/2003 ROBERT SHERRY WATER REVIEW Approved
11/07/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
11/10/2003 MVALDEZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2003 MONICA VALDEZ OUT TO CUSTOMER Completed