Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM05261
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet A1 1. Specify all window sizes. Sill heights and operability criteria for the bedroom must comply with IRC emergency escape and rescue requirements. Ref. R310. 2. Safety glazing is required for all windows within a 24" arc swing of doors. Ref. R308. Safety glazing is also required at the shower door. 3. Specify nonabsorbent surface finish to a height of 6' above the floor at the shower. Ref. R307. 4. Show the landing at the foyer exterior door. Ref. R312. PLUMBING COMMENTS Sheet MP1 1. Revise note 1 to indicate the 1994 UPC as amended to be the governing code. 2. Gas fired appliances are not permitted in sleeping rooms. Please revise. MECHANICAL COMMENTS Sheet MP1 1. In the revised plan, show combustion relief air provisions. ELECTRICAL COMMENTS Sheet E1 1. Specify ground fault circuit interrupter protection for the outdoor receptacle on the west side of the addition. 2. Provide means of disconnect for new A/C #2. 3. The IRC requires smoke alarms to be provides for the existing residence. Note this on sheet E1. Ref. R317. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/01/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |