Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide complete mechanical plan. Reference Section 106.3.1, IMC 2000.
2. Provide protection for openings in fire rated partitions and exit corridors. Reference Section 607, IMC 2000.
3. Provide calculations to show that adequate ventilation is being provided to the space. Reference Section 403.3, IMC 2000.
11/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plan. Reference Section103.2.3, UPC 1994.
11/19/2003 SREEVES1 WWM REVIEW Needs Review
11/19/2003 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review
11/19/2003 SREEVES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review