Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05256
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/06/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/07/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide complete plumbing plan. Reference Section103.2.3, UPC 1994. |
| 11/07/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | DENIED 11/7/03 1. Indicate conductor size on Panel feeder. Verify adequacy of sizing. DENIED 11/13/03 1. Provide phase conductors for Panel A. 791.5550 x1106 |
| 11/07/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/07/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide complete mechanical plan. Reference Section 106.3.1, IMC 2000. 2. Provide protection for openings in fire rated partitions and exit corridors. Reference Section 607, IMC 2000. 3. Provide calculations to show that adequate ventilation is being provided to the space. Reference Section 403.3, IMC 2000. |
| 11/13/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/13/2003 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 11/13/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |