Permit Number: T03CM05256
Parcel: 12803076B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05256
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2003 LOREN MAKUS ENGINEERING REVIEW Approved
11/06/2003 DAN CASTRO ZONING REVIEW Approved
11/07/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plan. Reference Section103.2.3, UPC 1994.
11/07/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 11/7/03
1. Indicate conductor size on Panel feeder. Verify adequacy of sizing.

DENIED 11/13/03
1. Provide phase conductors for Panel A.

791.5550 x1106
11/07/2003 ROBERT SHERRY WATER REVIEW Approved
11/07/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide complete mechanical plan. Reference Section 106.3.1, IMC 2000.
2. Provide protection for openings in fire rated partitions and exit corridors. Reference Section 607, IMC 2000.
3. Provide calculations to show that adequate ventilation is being provided to the space. Reference Section 403.3, IMC 2000.
11/13/2003 JIM EGAN FIRE REVIEW Approved
11/13/2003 SREEVES1 WWM REVIEW Needs Review
11/13/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2003 SUE REEVES OUT TO CUSTOMER Completed