Permit Number: T03CM05254
Parcel: 14108521C

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T03CM05254
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2003 DAN CASTRO ZONING REVIEW Approved
11/07/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise water pressure calculations to provide a minimum residual pressure of 15 PSI. Modify pipe sizing as required by revised calculations, including all branch pipes. Reference Section 608.1, UPC 1994.
2. Revise the fixture units for the sink to 4 units for water and 3 units for waste. Reference Tables 6-3 and 7-3, UPC 1994.
3. Provide expansion tank for water heater. Reference Section 608.3, UPC 1994.
4. Show size, route, and termination of temperature and pressure relief for water heater. Reference Section 608.5, UPC 1994.
11/07/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
11/07/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation for the project areas. Reference Section 403.3, IMC 2000.
2. Provide information showing how the condensate drains were sized. Reference Section 307.2.2, IMC 2000.
3. Provide protection of all duct penetrations through floor/ceiling assemblies and fire-resistance-rated assemblies. Reference Section 302.2, IMC 2000.
4. Provide the weight of the proposed mechanical equipment. Reference Section 302.1, IMC 2000.
5. Provide structural calculations and details for the equipment platform. Reference Section 302.1, IMC 2000.
11/07/2003 JIM EGAN FIRE REVIEW Z_DO NOT USE
11/07/2003 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2003 LISA LESNY OUT TO CUSTOMER Completed