Permit Number: T03CM05226
Parcel: 107010550

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05226
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2004 MARTIN HAEBERLE BUILDING-RESIDENTIAL REVIEW Denied 1. Provide a site plan showing location of the proposed building in relation to the property line and other structures.
Site plan provided indicates structure less than 3 feet from property line. Revise plans to show required firewall location and provide details of wall.
Further, no openings may be allowed in the firewall due to proximity to property line. References table 602 IBC. Still need to provide detail of wall. Must be a listed assembly.
2. Provide a detail sheet signed by the structural engineer reflecting details within calculations cross-referencing to the plans. Still need details for connections on plan sheet sealed by the engineer of record. Attached 81/2 x 11 are not acceptable.
3. It has come to my attention that the structure is already built. How are required footings and hold-down installations to be verified?
4. Obtain an appointment with plans examiner prior to resubmittal.