Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05226
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide a site plan showing location of the proposed building in relation to the property line and other structures. Site plan provided indicates structure less than 3 feet from property line. Revise plans to show required firewall location and provide details of wall. Further, no openings may be allowed in the firewall due to proximity to property line. Reference table 602 IBC 2. Provide a detail sheet signed by the structural engineer reflecting details within calculations cross-referencing to the plans. Still need details for connections. 3. Due to the proposed building is a passenger car garage the 20 # live load may not be reduced. Revise plans and calculations. References section 1607.9.1.2 IBC. 4. Site plan to include location of all service lines to buildings. Re: electrical, gas, water, and sewer |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 01/13/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |