Permit Number: T03CM05225
Parcel: 11206013A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05225
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2003 DAN CASTRO ZONING REVIEW Approved
11/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide additional information concerning the plumbing requirements for the misting areas: backflow protection, drain configuration, etc.
2. A 1/2" connection (public) is rated at 4 water fixture units, not 2. The correct total for the water in this project is 20 fixture units for a demand of 14 GPM. The maximum capacity of a 3/4" copper pipe is only 12 GPM.
11/13/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
11/13/2003 ROBERT SHERRY WATER REVIEW Approved
11/13/2003 JIM EGAN FIRE REVIEW Approved
11/13/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/13/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
11/14/2003 TACHONG1 WWM REVIEW Needs Review
11/14/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05225 DENIED 11/13/03
1. Power Plan indicates a connection to Panel A-19,21. No such loads on the Panel Schedule. Please add this load and rework Panel Load calculations as necessary.
2. On the Riser Diagram, the #6 GND needs to be #4. It is sized for the 3/0 conductors per NEC Table 250-66. See NEC 250-102 (c .
3. Provide available fault current at service, and demonstrate that the new Panel is within its AFC rating.

791.5550 x1106

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed