Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM05203
Parcel: 122152160

Address:
3364 E GRANT RD

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM05203
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2004 EROSE1 ENGINEERING REVIEW Stop
11/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show existing water supply piping and show that it has the capacity to allow the connection of the new fixture.
2. Show total length of new 1-1/2" vent.
11/03/2003 ANY WWM REVIEW Stopped
11/03/2003 ANY BUILDING-COMMERCIAL REVIEW Stopped
11/03/2003 ROBERT SHERRY WATER REVIEW Approved
11/03/2003 ANY ELECTRICAL-COMMERCIAL REVIEW Stopped
11/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that termination point for condensate drain can accept the flow without surface runoff.
2. Provide calculations demonstrating adequate ventilation for classroom.
3. Show routing and termination of the auxillary drain.
11/03/2003 ANY ZONING REVIEW Stopped
11/03/2003 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2003 ANY APPROVAL SHELF Stopped
11/03/2003 ANY OUT TO CUSTOMER Stopped
11/03/2003 ANY REJECT SHELF Stopped