Permit Number: T03CM05201
Parcel: 11707177A

Address:
644 S 5TH AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM05201
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 EROSE1 WWM REVIEW Needs Review
11/17/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet T-1
1. Please specify the horizontal joint reinforcement at 16" spacing for the 8" CMU wall shown in detail 1/T-1. Specify vertical reinforcement within 16" of the ends of the masonry walls. Ref. IBC 2106.4.1.3.

Sheet A-1
1. Show the 6th footing as detailed in 5/A-1 that occurs between the bath and kitchen.

STRUCTURAL COMMENTS - The structural portion has been reviewed and approved.

PLUMBING COMMENTS
Sheet P-1
1. Specify waste line and size for the clothes washer. Ref. UPC Table 7-5.


MECHANICAL COMMENTS
1. Please clarify the route and termination of the range hood or specify ventless hood. Ref. M1502.

ELECTRICAL COMMENTS
Sheet E-1
1. Additional convenience receptacles are required. See redlines. Ref 3801.2.

ENERGY COMMENTS
General
1. Please specify R-values for the insulation shown in the laundry room framing detail at 7/A-5.
11/17/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2003 ELAINE ROSE OUT TO CUSTOMER Completed