Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/17/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
11/17/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet T-1 1. Please specify the horizontal joint reinforcement at 16" spacing for the 8" CMU wall shown in detail 1/T-1. Specify vertical reinforcement within 16" of the ends of the masonry walls. Ref. IBC 2106.4.1.3. Sheet A-1 1. Show the 6th footing as detailed in 5/A-1 that occurs between the bath and kitchen. STRUCTURAL COMMENTS - The structural portion has been reviewed and approved. PLUMBING COMMENTS Sheet P-1 1. Specify waste line and size for the clothes washer. Ref. UPC Table 7-5. MECHANICAL COMMENTS 1. Please clarify the route and termination of the range hood or specify ventless hood. Ref. M1502. ELECTRICAL COMMENTS Sheet E-1 1. Additional convenience receptacles are required. See redlines. Ref 3801.2. ENERGY COMMENTS General 1. Please specify R-values for the insulation shown in the laundry room framing detail at 7/A-5. |
11/17/2003 | EROSE1 | NPPO | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/17/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |