Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM05199
Parcel: 127035470

Review Status: Completed

Review Details: 3RD PARTY REVIEW-CELL TOWER/ANTENNAS

Permit Number - T03CM05199
Review Name: 3RD PARTY REVIEW-CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2003 EROSE1 OPERATIONS REVIEW Needs Review
11/20/2003 ELAINE ROSE PLANNING-CITY HALL REVIEW Needs Review
11/20/2003 EROSE1 FIRE REVIEW Needs Review
11/20/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q Sheet C-2 indicates with a note that the roofing is to be removed under the "platform". The platform is a "raised" platform (there are bearing plates which support the platform 12" off of the roof). The platform is a grate and will allow water through to the roof below. What protects the roof deck from this water now that the roofing is gone?

STRUCTURAL:

q There are no structural comments to be addressed.

ELECTRICAL:

q The typical grounding system diagram on Sheet E4 indicates has keyed note No. 6 in two places, however the grounding notes list indicates that note no. 6 is not used. Please clarify. Also, there is no clear reference to bonding the metal equipment platform.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2003 ELAINE ROSE OUT TO CUSTOMER Completed