Permit Number: T03CM05181
Parcel: 13419042C

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM05181
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2003 EROSE1 WWM REVIEW Needs Review
12/02/2003 EROSE1 ENGINEERING REVIEW Needs Review
12/02/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q Please coordinate some of the recent changes made to the plans:
· Check keyed notes on Sheet S3.1. Notes added to the list were numbers 11, 12, and 13. The framing plan shows new notes 7, 8, and 9.
· Detail T15 on Sheet S1.2 and Detail T23 on Sheet S1.3 now indicate 5 1/8" x 12" glue laminated beams (versus the 6x12 originally indicated), while Detail T24 still indicates the 6x12.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
12/02/2003 ELAINE ROSE ZONING REVIEW Needs Review
12/02/2003 EROSE1 WATER REVIEW Needs Review
12/02/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2003 ELAINE ROSE OUT TO CUSTOMER Completed