Permit Number: T03CM05171
Parcel: 13316030E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05171
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/30/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/31/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/31/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Completed
10/31/2003 ROBERT SHERRY WATER REVIEW Approved
10/31/2003 JTUCKER FIRE REVIEW Approved
10/31/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/06/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Provide a disconnect for the X-Ray Equipment, per NEC 517-72. The number and size of the 6 "X-Ray" circuits leaves one wondering whether there is some major piece of equipment not shown on the plans. Please submit cut sheets for X-Ray equipment, if new, or if existing, please document such on the plans. Do the dental chairs need power?
2. Circulating Pump CP-1 is listed on Sheet P1 as 120/1, 1/25. No such equipment is indicated on Power Plan or Panel Schedules.
3. Two motor loads appear on the Power Plan, Circuits 9 and 27. No such accounting on Panel Schedule or Mechanical plans.
12/02/2003 MELISSA POULIN WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2003 TAMI ACHONG OUT TO CUSTOMER Completed