Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05159
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
10/30/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Z_DO NOT USE | |
10/30/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/30/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
11/04/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/04/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
11/04/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
11/04/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/04/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05159 DENIED 10/30/03 1. Phase C on Panel P, load calculation comes to 15,680, and 131 amps, which exceeds the bus capacity of 125A. Reconfigure circuitry, and revise load calculations. 2. Existing Panel P feeds new Panel N. On line diagram Panel L feeds Panel N. Please clarify. 3. Please put Panel P in the Line Diagram. LAB 791-5550 X1106 |