Permit Number: T03CM05159
Parcel: 14029052C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05159
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2003 JIM EGAN FIRE REVIEW Approved
10/30/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
10/30/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/30/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/04/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/04/2003 GERRY KOZIOL WWM REVIEW Approved
11/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/04/2003 ROBERT SHERRY WATER REVIEW Approved
11/04/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05159 DENIED 10/30/03
1. Phase C on Panel P, load calculation comes to 15,680, and 131 amps, which exceeds the bus capacity of 125A. Reconfigure circuitry, and revise load calculations.
2. Existing Panel P feeds new Panel N. On line diagram Panel L feeds Panel N. Please clarify.
3. Please put Panel P in the Line Diagram.