Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM05157
Parcel: 117143510

Address:
448 S MAIN AV

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05157
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2003 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS PROJECT #T03CM05157

1-Dec-03 448 S. MAIN AVENUE

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SECTIONS - DETAILS - MISC. NOTES:
1. DETAIL AND NOTE ALL MASONRY WALL REINFORCEMENT PER R606.11.2.2.3. ADD MASONRY BOND BEAM AT LEDGER ANCHOR BOLT LEVEL.

2. DETAIL LEDGER ATTACHMENT TO INTERIOR WOOD FRAME WALL. (EXISTING DETAIL SHOWS NO ATTACHMENT METHOD).

3. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312. (MUST SLOPE AWAY FROM BUILDING)

STRUCTURAL:
1. DETAIL LEDGER ATTACHMENT AT PORCH ROOFS.

2. PROVIDE HEADER SCHEDULE FOR INTERIOR BEARING WALL AND SPAN ACROSS OPENING OF PRE-EXISTING WALL.

PLUMBING PLANS:
1. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

2. THE CITY OF TUCSON HAS ADOPTED THE 1994 UPC WITH THE STATE AMENDMENTS (ARIZONA STATE PLUMBING CODE). ALL PLANS MUST REFERENCE THIS CODE.

MECHANICAL PLANS:
1. SPECIFY SIZE OF RETURN AIR GRILL.

ELECTRICAL PLANS:
1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. 30 AMP CIRCUIT FOR 80 GAL WATER HEARTER SEEMS INADEQUATE, PLEASE PROVIDE WATER HEATER SPECIFICATIONS TO SHOW JUSTIFICATION FOR 30 AMP.

3. ALL RECEPTACLE OUTLETS IN BATHROOMS, KITCHENS, AND UNFINISHED BASEMENTS SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION, PER E3802.

4. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP. IF EXITING ROOMS #1 AND #2 MAY BE USED FOR SLEEPING PURPOSES, PROVIDE SMOKE DETECTORS.

MODEL ENERGY CODE:
1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. YOUR PLAN SHOWS NO INSULATION IN EXTERIOR WALLS OR ROOF / CEILING SYSTEM.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
BRUCE STEVENS @ 791-5550 EXT. 1174

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2003 LISA LESNY OUT TO CUSTOMER Completed
12/01/2003 LISA LESNY REJECT SHELF Completed
12/01/2003 LISA LESNY APPROVAL SHELF Completed