Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05129
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/29/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/30/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/30/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/30/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/31/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/05/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/05/2003 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 11/05/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05129 DENIED 10/31/03 1. Establish/bond to a Grounding Electrode System at Panel C per NEC 250-32. It appears that 250-32 (b) (1) would be most applicable in this case, and the Handbook has a good discussion. 2. Panel Schedule B shows total of 111.5 A. Load Calculation shows 94. Please clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |