Permit Number: T03CM05129
Parcel: 111070240

Address:
3333 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05129
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2003 JIM EGAN FIRE REVIEW Approved
10/29/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/30/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/30/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
10/30/2003 ROBERT SHERRY WATER REVIEW Approved
10/31/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/05/2003 DAN CASTRO ZONING REVIEW Approved
11/05/2003 MELISSA POULIN WWM REVIEW Approved
11/05/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05129 DENIED 10/31/03
1. Establish/bond to a Grounding Electrode System at Panel C per NEC 250-32. It appears that 250-32 (b) (1) would be most applicable in this case, and the Handbook has a good discussion.
2. Panel Schedule B shows total of 111.5 A. Load Calculation shows 94. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed