Permit Number: T03CM05127
Parcel: 13321074A

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM05127
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2004 EROSE1 WWM REVIEW Stop
10/29/2003 JIM EGAN FIRE REVIEW Approved
10/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.
10/29/2003 ROBERT SHERRY WATER REVIEW Approved
10/29/2003 DAN CASTRO ZONING REVIEW Approv-Cond
10/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/29/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05127 DENIED 10/29/03
1. Provide Panel and circuit numbers for all lighting fixtures.
2. Provide panel schedule and feeder load calculations.
10/29/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2003 ANY APPROVAL SHELF Stopped
10/28/2003 ANY OUT TO CUSTOMER Stopped
10/28/2003 ANY REJECT SHELF Stopped