Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05120
Parcel: 13419042D

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM05120
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2003 EROSE1 WWM REVIEW Needs Review
12/01/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q The mechanical units for this project are new. How do they compare to what existed on the roof previously as far as weight and location? At 1,832 lbs each for the 4 larger units and 1,000 lbs for the 1 small unit, is the roof capable of supporting this additional weight at these locations? Please clarify. This previous comment has been addressed, however field welding has been added to the scope of the job which requires a special inspection certificate. Please provide a City of Tucson special inspection certificate for field welding.

MECHANICAL:

q There are no mechanical comments to address.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
12/01/2003 EROSE1 WATER REVIEW Needs Review
12/01/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2003 ELAINE ROSE OUT TO CUSTOMER Completed