Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM05119
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 12/04/2003 | EROSE1 | ENGINEERING | REVIEW | Needs Review | |
| 12/04/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | SCOPE OF REVIEW: The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q The description of Wall Types "D" and "E" are confusing relative to Details 5, 8, and 9 on Sheet A3.0. Based on the description in the Wall Legend it appears that Wall Type "D" is: ยท For the lower 48", a concrete wall. The upper portion of the wall above 48" is then two parallel stud wall partitions with 2 layers of 5/8" type "X" gypsum board on the outside of each parallel wall, filled with fiberglass batt insulation (what thickness or R-value?) and with a layer of steel security mesh in this assembly somewhere. The concrete face of the lower wall is to align with the face of the gypsum board (Detail 8 does not show it this way). Detail 8 is noted in the legend but it does not fit this description. Only one framed wall is shown (a second is noted but when does it occur?) Where is the security mesh? Detail 5 shows only a single layer of gypsum on both sides (is it to be a single layer at Wall Type "F" and two layers at Detail "D"?) Is Wall Type "E" the same except that the lower 48" concrete wall has hat channels and 1 layer of 5/8" gypsum board on both sides of the concrete wall? Detail 9 is referenced but where are the hat channels? Detail 8 shows hat channels but they are not noted. Detail 8 is supposed to coordinate with Wall Type "D" which implies that the concrete wall is exposed with no hat channels and gypsum board. Please coordinate the descriptions of these wall types and the details. This previous comment has been partially addressed. The wall type descriptions have been modified, but the details still don't make sense relative to the descriptions. Reference attached sheets for further comments. STRUCTURAL: q There are no structural comments to be addressed. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q A fault current calculation has been provided on Sheet E1.0 (and the Alt. E1.0 as well). However, fault rating has not been indicated for any of the equipment. Is this to be a series rated system? What is to be the rating of the panels? Please clarify. This previous comment has not been addressed. -End of Review- |
| 12/04/2003 | ELAINE ROSE | ZONING | REVIEW | Needs Review | |
| 12/04/2003 | EROSE1 | WATER | REVIEW | Needs Review | |
| 12/04/2003 | EROSE1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |