Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05113
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/28/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/28/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/28/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/28/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 10/28/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/28/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/28/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/28/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |