Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2003 Joseph Linville LANDSCAPE REVIEW Denied 1) Refuse containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises. DS 6-01.4.1.I

2) The street landscape border is required to be a minimum of ten feet wide along the entire street frontage. The buffer is required to be located entirely on site unless the City Engineer approves a portion of the code required landscape buffer in the public right of way. Revise the plan provide the full 10" buffer on site west of the ingress/egress location or obtain approval from the City Engineer in writing.
LUC 3.7.2.4.A.3
11/18/2003 JOE LINVILLE NPPO REVIEW Approved Exception.
11/20/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate current property legal description and tax code. If there are more than one lots involved specify legal description for each lot. D.S. 2-02.2.1.A.2

2. Indicate roof slope. D.S. 2-02.2.1.A.6

3. Indicate, if applicable, location, type, size and height of existing and proposed signage. D.S. 2-02.2.1.A.13

4. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades on Site Plan. D.S. 2-02.2.1.A.16

5. Dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way. D.S. 2-02.2.1.A.19

6. All easements of record must be graphically shown on the plan together with recording docket and page reference. Indicate to whom the alley east of the property to be abandoned/dedicated to. D.S. 2-02.2.1.A.20

7. Indicate existing and proposed dimensioned curbs, sidewalks, driveways and utility lines. D.S. 2-02.2.1.A.21

8. Existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. Indicate this information on the Site Plan. D.S. 2-02.2.1.A.23

9. New projects consisting of three or more dwelling units are required to provide centralized on-site refuse storage, collection, and pickup areas. Relocate refuse collection area. Refer to development standard D.S.6-01.2.2 for design specifications. Collection vehicles are not allowed to backup onto on coming traffic. Contact Environmental Services @ 791-3175 ext.1136, John Clark for curbside pickup. Refuse container area is to be 10' x 10'.

10. Site Plan, sheet C1.1, identify broken line in P.A.A.L. area outlining building area.
11/24/2003 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
Submittal, which states how all Zoning Review Section comments Regarding the Land Use Code and Development Standards were Addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Note the legal description of the property. (D.S. 2-02.2.1.A.2)

2. Note the square footage of the studios. The information is required to verify the correct vehicle parking ratio for the proposed studios. (LUC 3.3.4) (D.S. 2-02.2.1.A.8)

3. One (1) van accessible parking space is required. Access aisle must be minimum eight (8) foot wide. Revise as required. (2000 IBC Section 1106.4)

4. Dimension the back-up spur radii. Three (3) foot radii required. (D.S. 3-05.2.3.C.2) (D.S. 2-02.2.1.A.11)
5. If patio cover is proposed west of apartment building, please label and dimension roof area and height. If roof cover is proposed, a minimum one (1) foot setback is required from a 24' wide PAAL. If applicable, label and dimension setback. (D.S. 3-05.2.2.B.2)

6. Provide the density calculation. Refer to LUC Sec. 3.2.10 for explanation of residential density calculation.

7. All requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A)

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
11/25/2003 DAN CASTRO HANDICAP-SITE REVIEW Denied One (1) van accessible parking space is required. Access aisle must be minimum eight (8) foot wide. Revise as required. (2000 IBC Section 1106.4)
12/02/2003 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
12/02/2003 ANGIE SHOFFSTALL REJECT SHELF Completed