Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM05100
Parcel: 13510150R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05100
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2003 JIM EGAN FIRE REVIEW Approved
10/27/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide data from manufacturer of pedicure that indicates that an appropriate air gap is provided for the water fill of each pedicure or provide a reduced pressure backflow preventer assembly for each hot and cold water connection.
10/27/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Passed
10/27/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide Manufacturer, operating information and electrical data for the new exhaust fan.
2. Revise ventilation calculations to comply with Section 403.3, IMC 2000. The closest category to a nail salon is a beauty parlor which requires 25 CFM per person. The breakroom requires outside air based on Table 403.3; The restroom may use transfer air (see Section 403.2.2, IMC 2000); and provide air flowrate for all diffusers to allow application of Equation 4.1 to evaluate the common ventilation rate or base the outside air requirements on the space having the largest outside air requirement. The minimum exhaust requirement for restrooms is 75 CFM per urinal or water closet (Table 403.3, IMC 2000).
10/27/2003 JIM TATE ENGINEERING REVIEW Approved
10/29/2003 ROBERT SHERRY WATER REVIEW Approved
10/29/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05100 DENIED 10/27/03
1. Manual calls for hard-wiring, which implies EPO per NEC 680-38, as opposed to receptacles.
2. Circuit needs to be GFCI per Manual and NEC 680-41 (a) (3) if indeed plug and cord connected.
3. Provide/address receptacles per 680-41 (a) (1) & (2).
4. Verify/document that lighting fixtures meet the requirements of NEC 680-41 (b) (1).
10/30/2003 CAGUILA1 WWM REVIEW Needs Review
10/30/2003 CAGUILA1 ZONING REVIEW Needs Review