Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05100
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/27/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide data from manufacturer of pedicure that indicates that an appropriate air gap is provided for the water fill of each pedicure or provide a reduced pressure backflow preventer assembly for each hot and cold water connection. |
| 10/27/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 10/27/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide Manufacturer, operating information and electrical data for the new exhaust fan. 2. Revise ventilation calculations to comply with Section 403.3, IMC 2000. The closest category to a nail salon is a beauty parlor which requires 25 CFM per person. The breakroom requires outside air based on Table 403.3; The restroom may use transfer air (see Section 403.2.2, IMC 2000); and provide air flowrate for all diffusers to allow application of Equation 4.1 to evaluate the common ventilation rate or base the outside air requirements on the space having the largest outside air requirement. The minimum exhaust requirement for restrooms is 75 CFM per urinal or water closet (Table 403.3, IMC 2000). |
| 10/27/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 10/29/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/29/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05100 DENIED 10/27/03 1. Manual calls for hard-wiring, which implies EPO per NEC 680-38, as opposed to receptacles. 2. Circuit needs to be GFCI per Manual and NEC 680-41 (a) (3) if indeed plug and cord connected. 3. Provide/address receptacles per 680-41 (a) (1) & (2). 4. Verify/document that lighting fixtures meet the requirements of NEC 680-41 (b) (1). |
| 10/30/2003 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 10/30/2003 | CAGUILA1 | ZONING | REVIEW | Needs Review |