Permit Number: T03CM05073
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05073
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2003 LOREN MAKUS ENGINEERING REVIEW Approved
10/23/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2003 ANY BUILDING-COMMERCIAL REVIEW Passed
10/29/2003 ROBERT SHERRY WATER REVIEW Passed
10/29/2003 JIM EGAN FIRE REVIEW Approved
10/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/07/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 10/30/03 T03CM05073
1. Sheet E1, Keynotes 6, 9, & 5. Per NEc 400-8, flexible cords and cables shall not be used where concealed behind dropped ceilings. Suggest one of the following:
A: If the equipment being plugged into the above ceiling receptacles does not have a cord and plugs in directly, such as a low-voltage transformer, change the duplex to simplex receptacle.
B: If the equipment has a cord, suggest a J-box for the receptacle and flexible conduit for the cord.
3. Note that as in job T03CM05074, reviewed yesterday, demand factors for continuous loads shall be calculated at 125%. However, on this job such consideration does not appear to be critical to ultimate loading.

Linda Buczynski
520.791.5550 x1106
11/07/2003 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2003 TAMI ACHONG OUT TO CUSTOMER Completed