Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05055
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | Site plan approval is required. |
| 11/05/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plans showing the complete oxygen and vacuum piping systems. Show how the oxygen and vacuum piping systems comply with the requirements of NFPA 99 (1996 edition). Reference Appendix F, UPC 1994, as amended by the State of Arizona. |
| 11/05/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/05/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise outside air calculations for the addition to comply with the requirements of Section 403.3.2, IMC 2000. 2. Provide ventilation calculations for the revised second floor. Reference Sections 403.3 and 403.3.2, IMC 2000. 3. Provide information to show how the proposed HVAC system will be able to comply with the manufacturer's temperature and humidity requirements. Reference Section 304.1, IMC 2000. |
| 11/19/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. WILL ENTER LATER. |
| 11/19/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T03CM05055 .. DGL .. 11/19/03 .. 141 E FORT LOWELL .. S1. PROVIDE COMPLETE " COMMERCIAL PLAN SUBMITTAL CHECKLIST", ATTACHED (SEE DSD WEBSITE). S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST , ATTACHED (SEE DSD WEBSITE). S3. LOCATE ADDITION, BY DIMENSION, FROM TWO ADJACENT PROPERTY LINES, ON SITE PLAN. S4. INDICATE WALL FIRE-RATINGS DUE TO PROXIMATRY TO PROPERTY LINES, PER SITE PLAN AND IBC SEC #5, #6, AND #7. CALLOUT : FIRE WALLS, FIRE-RATINGS AND LISTINGS ON DRAWINGS. S5. SHOW, ON SITE DRAWING #C-1, LOCATION OF PREMISES IDENTIFICATION CONFORMING TO IBC SEC #501.2 AND PIMA COUNTY ADDRESSING ORDINANCE. S6. PROVIDE COST ESTIMATE WITH ACCESSIBILITY ITEMS LISTED TO SHOW CONFORMANCE WITH IBC SECTION # 3408. S7. CLARIFY INTERIOR FINISHES CONFORMANCE WITH IBC SEC #8, TABLE # 803.4, INDICATE ON DRAWINGS. S8. CLARIFY EXITING. S9. CLARIFY FIRE-RATINGS AT EXITING, INCLUDING PORCH ADDITION. S10. SHOW COMPLETE CONNECTION DETAILS OF PARTITIONS TO STRUCTURE ABOVE AND BELOW, FOR VAIOUS CONDITIONS, WITH MATERIALS OF CONSTRUCTION AND FASTENERS CALLED OUT, INCLUDING BRACING CONNECTIONS. S11. SPECIFY ROOF FLASHING GAUGE, PER IBC SEC #14, TABLE 1405.2. S12. INDICATE CEILING SUSPENSION SYSTEM MANUFACTURER AND MODEL NUMBER, ON DRAWINGS OR FULLY DETAIL SUSPENSION SYSTEM. S13. PROVIDE COMPLETE FIRE DETAILING AND LISTINGS FOR FIRE-RATED ASSEMBLIES USED. S14. SPECIFY FLAME-SPREAD AND SMOKE-DEVELOPMENT FOR INSULATION IN ROOF AND WALL FURRED AREAS. S15. DETAIL METAL ROOFING ATTACHMENT TO WOOD ROOF DECK. S16. SPECIFY BUILT-UP ROOF COVERING CLASSIFICATION, PER IBC SEC #15. S17. PROVIDE COMPLETED INSPECTION PROGRAM, AS REQUIRED BY 1997 UNIFORM ADMINISTRATIVE CODE SECTION #302.5. S18. SPECIAL INSPECTION REQUIRED FOR : 1. SOILS 2. STRUCTURAL MASONRY 3. CONCRETE 4. EPOXY ANCHORS 5. EXPANSION ANCHORS. S19. SHOP DRAWINGS REQUIRED FOR TRUSSES. |
| 11/21/2003 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 11/24/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 11/26/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/05/2003 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/09/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 12/05/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |