Permit Number: T03CM05055
Parcel: 10603066A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05055
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2003 PATRICIA GILBERT ENGINEERING REVIEW Denied Site plan approval is required.
11/05/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied Provide plans showing the complete oxygen and vacuum piping systems. Show how the oxygen and vacuum piping systems comply with the requirements of NFPA 99 (1996 edition). Reference Appendix F, UPC 1994, as amended by the State of Arizona.
11/05/2003 ROBERT SHERRY WATER REVIEW Approved
11/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise outside air calculations for the addition to comply with the requirements of Section 403.3.2, IMC 2000.
2. Provide ventilation calculations for the revised second floor. Reference Sections 403.3 and 403.3.2, IMC 2000.
3. Provide information to show how the proposed HVAC system will be able to comply with the manufacturer's temperature and humidity requirements. Reference Section 304.1, IMC 2000.
11/19/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION. WILL ENTER LATER.
11/19/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T03CM05055 .. DGL .. 11/19/03 .. 141 E FORT LOWELL ..
S1. PROVIDE COMPLETE " COMMERCIAL PLAN SUBMITTAL CHECKLIST", ATTACHED (SEE DSD WEBSITE).
S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST , ATTACHED (SEE DSD WEBSITE).
S3. LOCATE ADDITION, BY DIMENSION, FROM TWO ADJACENT PROPERTY LINES, ON SITE PLAN.
S4. INDICATE WALL FIRE-RATINGS DUE TO PROXIMATRY TO PROPERTY LINES, PER SITE PLAN AND IBC SEC #5, #6, AND #7. CALLOUT : FIRE WALLS, FIRE-RATINGS AND LISTINGS ON DRAWINGS.
S5. SHOW, ON SITE DRAWING #C-1, LOCATION OF PREMISES IDENTIFICATION CONFORMING TO IBC SEC #501.2 AND PIMA COUNTY ADDRESSING ORDINANCE.
S6. PROVIDE COST ESTIMATE WITH ACCESSIBILITY ITEMS LISTED TO SHOW CONFORMANCE WITH IBC SECTION # 3408.
S7. CLARIFY INTERIOR FINISHES CONFORMANCE WITH IBC SEC #8, TABLE # 803.4, INDICATE ON DRAWINGS.
S8. CLARIFY EXITING.
S9. CLARIFY FIRE-RATINGS AT EXITING, INCLUDING PORCH ADDITION.
S10. SHOW COMPLETE CONNECTION DETAILS OF PARTITIONS TO STRUCTURE ABOVE AND BELOW, FOR VAIOUS CONDITIONS, WITH MATERIALS OF CONSTRUCTION AND FASTENERS CALLED OUT, INCLUDING BRACING CONNECTIONS.
S11. SPECIFY ROOF FLASHING GAUGE, PER IBC SEC #14, TABLE 1405.2.
S12. INDICATE CEILING SUSPENSION SYSTEM MANUFACTURER AND MODEL NUMBER, ON DRAWINGS OR FULLY DETAIL SUSPENSION SYSTEM.
S13. PROVIDE COMPLETE FIRE DETAILING AND LISTINGS FOR FIRE-RATED ASSEMBLIES USED.
S14. SPECIFY FLAME-SPREAD AND SMOKE-DEVELOPMENT FOR INSULATION IN ROOF AND WALL FURRED AREAS.
S15. DETAIL METAL ROOFING ATTACHMENT TO WOOD ROOF DECK.
S16. SPECIFY BUILT-UP ROOF COVERING CLASSIFICATION, PER IBC SEC #15.
S17. PROVIDE COMPLETED INSPECTION PROGRAM, AS REQUIRED BY 1997 UNIFORM ADMINISTRATIVE CODE SECTION #302.5.
S18. SPECIAL INSPECTION REQUIRED FOR :
1. SOILS
2. STRUCTURAL MASONRY
3. CONCRETE
4. EPOXY ANCHORS
5. EXPANSION ANCHORS.
S19. SHOP DRAWINGS REQUIRED FOR TRUSSES.
11/21/2003 GERRY KOZIOL WWM REVIEW Passed
11/24/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
11/26/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/05/2003 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/05/2003 ANGIE SHOFFSTALL REJECT SHELF Completed