Permit Number: T03CM05032
Parcel: 132111540

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM05032
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2003 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM05032
11/19/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. PLAN MUST BE APPROVED BY ZONING AND FLOODPLAIN.

FOUNDATION PLANS:

1. ALL EPOXY WORK BEING DONE WILL REQUIRE A SPECIAL INSPECTION. PROVIDE SPECIAL INSECTION FORM.

FLOOR PLANS:

1. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.------FOR BEDROOMS WHERE WINDOWS ARE BEING REPLACED.

- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

2. A ONE HOUR FIREWALL IS REQUIRED BETWEEN UNITS FROM THE FOUNDATION TO THE BOTTOM OF THE ROOF SHEATHING. PROVIDE LOCATION AS WELL AS DETAIL HOW WALL WILL BE CONSTUCTED.

STRUCTURAL PLANS:

1. AT THE CARPORT, THE CENTER 4X8 BEAM IS NOT ADEQUATE. CHANGE OR SUBMIT CALCS. TO JUSTIFY.

PLUMBING PLANS:

1. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.

ELECTRICAL PLANS:

1. IT APPEARS THAT BOTH UNITS ARE BEING TOTALLY REWIRED. IF NOT INDICATE EXISTING AND NEW. IF SO THEN STRUCTURES MUST COMPLY WITH THE IRC 2000 ELEC. ------SEE BELOW

2. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER
OUTLETS AND SWITCHES. ---RECEPTS MISSING IN BEDROOMS, AND LIVING ROOM.

3. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP.
IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
11/18/2003 DAVID RIVERA ZONING REVIEW Denied
11/20/2003 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
11/20/2003 ANGIE SHOFFSTALL REJECT SHELF Completed