Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM05025
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2004 | EROSE1 | WWM | REVIEW | Needs Review | |
| 02/18/2004 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | SCOPE OF REVIEW: The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q There are no structural comments to be addressed. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q Provide fault current information. The panel schedule on Sheet E2 indicates that the new panel has an A.I.C. rating of 10,000 and no fault current calculations have been provided to substantiate this rating. We are in receipt of another permit submittal for the tenant improvement (T04CM00511) that does provide a fault current calculation and indicates that the fault current at the connection point of the new panel is 55,600. -End of Review- |
| 02/18/2004 | EROSE1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/18/2004 | ELAINE ROSE | OUT TO CUSTOMER | Completed |