| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs to build public sewer (lot does not front public sewer). |
| 12/24/2003 | PIMA COUNTY | BUILDING-RESIDENTIAL | REVIEW | Denied | Plumbing: 1. 80 cfh input to furnace plus 65 cfh to range = 145 cfh @ 60 lf sizing run will require a 1" gas line; however, 3/4" is shown. Please review, revise as required and resubmit. Mechanical: 1. Detail interface between evaporative cooler ductwork and furnace ductwork. 2. Specify furnace cfm output. Shall equal floor plan distribution. 3. Provide unit control thermostat. 4. Provide toilet exhaust fans or note bathroom windows as openable. |