Permit Number: T03CM04984
Parcel: 131070650

Review Status: Completed

Review Details: REVISION

Permit Number - T03CM04984
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide revised water pressure and pipe sizing calculations for building 2 to identify the nature of the "water treatment" demand on sheet P0.1. Reference Section 610.1, UPC 1994.
2. Coordinate the size of the common water supply to building 2 and the central plant enclosure as shown on the plumbing site plan on sheet P1.1 with the water pressure and pipe sizing calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2005 JMORALE1 OUT TO CUSTOMER Completed
06/30/2005 SUE REEVES REJECT SHELF Completed