Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM04984
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide revised water pressure and pipe sizing calculations for building 2 to identify the nature of the "water treatment" demand on sheet P0.1. Reference Section 610.1, UPC 1994. 2. Coordinate the size of the common water supply to building 2 and the central plant enclosure as shown on the plumbing site plan on sheet P1.1 with the water pressure and pipe sizing calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 06/30/2005 | SUE REEVES | REJECT SHELF | Completed |