Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM04984
Parcel: 131070650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04984
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2005 GERRY KOZIOL WWM REVIEW Approved
03/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a copy of the approved sheets for comparison with the revised plans.
2. Comment not addressed. Provide revised water pressure and pipe sizing calculations for building 2 to reflect the addition of the central plant enclosure to the existing water meter. Note that the minimum required water pressure for the emergency shower is 30 psig. Reference Section 610.1, UPC 1994.
3. Comment not addressed. Coordinate the size of the water supply to building 2 and the central plant enclosure as shown on the plumbing site plan on sheet P1.1 with the pipe sizes shown on the central plant enclosure detail shown on sheet P1.1 and the water pipe sizes for building 2 as shown on sheet P2.4.
4. Comment not addressed. Clarify the design of the building sewer piping intersection south of building 2. Reference Section 311.2, UPC 1994.
5. Comment not addressed. Provide a drain, vent and cleanout for sink S-1. Reference Section 304.0, UPC 1994.
6. Comment not addressed. Provide an upper terminal cleanout for the 2" floor sink located near B-2. Reference Section 707.4, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2005 GBONILL1 OUT TO CUSTOMER Completed
06/28/2005 SUE REEVES REJECT SHELF Completed