Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04984
Parcel: 131070650

Review Status: Completed

Review Details: REVISION

Permit Number - T03CM04984
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved sheets for comparison with the revised plans.
2. Provide revised water pressure and pipe sizing calculations for building 2 to reflect the addition of the central plant enclosure to the existing water meter. Note that the minimum required water pressure for the emergency shower is 30 psig. Reference Section 610.1, UPC 1994.
3. Coordinate the size of the water supply to building 2 and the central plant enclosure as shown on the plumbing site plan on sheet P1.1 with the pipe sizes shown on the central plant enclosure detail shown on sheet P1.1 and the water pipe sizes for building 2 as shown on sheet P2.4.
4. Clarify the relationship of the 4" building sewer as shown on the plumbing site plan on sheet P1.1 with the 4" building sewer shown in the central plant enclosure detail shown on sheet P1.1.
5. Clarify the design of the building sewer piping intersection south of building 2. Reference Section 311.2, UPC 1994.
6. Provide a drain, vent and cleanout for sink S-1. Reference Section 304.0, UPC 1994.
7. Provide an upper terminal cleanout for the 2" floor sink located near B-2. Reference Section 707.4, UPC 1994.
03/02/2005 GERRY KOZIOL WWM REVIEW Denied NEED TO SEE ORIGINAL APPROVED PLANS

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/23/2005 SUE REEVES REJECT SHELF Completed