Permit Number: T03CM04982
Parcel: 131070650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04982
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a copy of the approved sheets for comparison with the revised plans.
2. Comment not addressed. Provide cleanouts in the building drain at intervals not exceeding 100 feet. Reference Section 707.4, UPC 1994.
3. Comment not addressed. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994.
04/07/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2005 GBONILL1 OUT TO CUSTOMER Completed
06/28/2005 SUE REEVES REJECT SHELF Completed