Permit Number: T03CM04982
Parcel: 131070650

Review Status: Completed

Review Details: REVISION

Permit Number - T03CM04982
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved sheets for comparison with the revised plans.
2. Clarify the design of the building sewer piping intersection west of building 1. Reference Section 311.2, UPC 1994.
3. Provide cleanouts in the building drain at intervals not exceeding 100 feet. Reference Section 707.4, UPC 1994.
4. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994.
03/02/2005 GERRY KOZIOL WWM REVIEW Denied NEED TO SEE ORIGINAL APPROVED PLANS

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/23/2005 SUE REEVES REJECT SHELF Completed