Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM04982
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a copy of the approved sheets for comparison with the revised plans. 2. Clarify the design of the building sewer piping intersection west of building 1. Reference Section 311.2, UPC 1994. 3. Provide cleanouts in the building drain at intervals not exceeding 100 feet. Reference Section 707.4, UPC 1994. 4. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994. |
| 03/02/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO SEE ORIGINAL APPROVED PLANS |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 03/23/2005 | SUE REEVES | REJECT SHELF | Completed |