Permit Number: T03CM04982
Parcel: 131070650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04982
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Revise ventilation calculations for areas served by a common air handler. Reference Section 401, IMC 2000.
04/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the size of the water line feeding the central plant enclosure as shown on the plumbing site plan with the size shown on the central plant enclosure drawing.
04/19/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied As discussed this afternoon with Mr. Bollin the following items need to be addressed:
1.Electrical plans examiner pointed out a site light pole is over 20 feet. Structural plans and drawing will be required for this pole. Please submit for review.
2. Items previously addressed as of e-mail dated 1/8/04 are not incorporated in these plans. see below

Martin:

Happy New Year! I will be in Tucson tomorrow and would like to submit the
information that is listed below to get the structural and architectural
approval of the plans.

Please let me know if you are in the office in the late morning or early
afternoon.

Thanks,

Robert
714-504-1982

-----Original Message-----
From: Martin Haeberle [mailto:MHaeber1@ci.tucson.az.us]
Sent: Friday, January 02, 2004 1:46 PM
To: Robert Bollin
Cc: David Mann
Subject: Jim Click Ford


Robert,

I have received and reviewed the revised mezzanine calculations and found
them in compliance with the IBC.
As discussed with Mr. Mountjoy and Mr. Flynn, the following will be
incorporated into the plans:
1. Details reflecting penetration of the 2 hour assembly to reference fire
penetrations criteria specified within plans.
2. Remove statement in regards to having less than 15 employees exempts them
from providing male/ female restrooms.

Upon formal submittal of the final documents, with these revisions, the
architectural/ structural portion of the plans are approved.

If I can be of further assistance please feel free to contact me.

Martin
04/20/2004 GERRY KOZIOL WWM REVIEW Denied Bldg 1 - Jim Click Ford Dealership - includes central plant enclosure 4"CS and Bldg 2 - Car wash.
Needs WW/WC Tom Tomchak review of sand/oil interceptor - 579-5771
Needs WW review of connection to public sewer and review of status of existing on-site public sewer-8th floor - 740-6500
Needs WW/review of credit if applicable (no demo drawings) non-par unless WW reviews differently.
04/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E-1
1. In Keynotes 6, 7, 9 & 10, specify that the combination starter shall have overload protection, sized per manufacturer's recommendations. Having run a few calculations, it appears that the circuit breakers in Panels HP and LP are oversized to provide overload protection for these motor loads. They are sized properly for Ground Fault and Short Circuit protection only.

Sheet E-3
1. Feeder on the secondary to 15 KVA X'FMR, #10 GND is undersized. Smallest size per Table 250-66 is #8. Please note that, per Footnote 1 of Table 250-66, this Table applies to derived conductors of separately derived ac systems. Since there is no overcurrent protective device ahead of the transformer secondary conduit, Table 250-122 can not be used in this application.
2. Feeder on the secondary to 300 KVA X'FMR, 2/0 GND is undersized. Should be 3/0 per Table 250-66.
3. Feeder on the secondary to 225 KVA X'FMR, 1/0 GND is undersized. Should be 2/0 per Table 250-66.

Sheet E9
1. Provide overload protection for Air Compressor on Building #2 Power Plan, and all such equipment on this sheet. This may clear up after the clarification required in Comment #1 above is made. Same for the Dryer.

Sheet E-16
1. Provide calculations for both poles and foundations for any pole exceeding 20' in height. Needs approval from Martin Haeberle.
2. According to the Lighting Ordinance, Table 5, as applicable to this Area, any metal halide lighting source over 50W shall have full cutoff lighting distribution. As 175 W uplights, Fixtures K do not comply.
04/28/2004 DAVID RIVERA ZONING REVIEW Denied Two copies of the approved and stamped site plan and related sheets ust be included with the building plans packet.

Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
04/28/2004 ANGIE SHOFFSTALL REJECT SHELF Completed