Permit Number: T03CM04982
Parcel: 131070650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04982
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise ventilation calculations for areas served by a common air handler. Reference Section 401, IMC 2000.
12/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise reduced pressure backflow preventer to comply with the requirements of Section 610.2, UPC 1994.
2. Revise water supply to the emergency shower as needed to insure a minimum pressure of 30 PSIG.
3. Revise the size of the floor sink shown in detail 1/P2.3 to conform to Section 910.0, UPC 1994.