Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM04981
Parcel: 131080060

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM04981
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2003 GERRY KOZIOL WWM REVIEW Denied Needs 8th Floor WasteWater credit evaluation - 740-6500
12/09/2003 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM04981
12/9/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. PROVIDE THE LOCATIONS OF TEMPERED GLASS PER R308.4. ----------- WINDOWS WITHIN A 24" ARC OF EITHER VERTICAL EDGE OF A DOOR SHALL BE SAFETY GLASS.

2. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.------------IF APPLIES. ROOF SLOPE IS NOT INDICATED.

3. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

4. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A
CLEAR SPACE IN FRONT OF NOT LESS THAN 21" PER R307.2 (FIGURE).

5. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. CLEARLY INDICATE AND DETAIL WHAT EXISTING WALLS ARE CONSTRUCTED OF AND WHAT THE INFILL WALLS WILL BE CONSTRUCTED OF.

2. PROVIDE SIZE AND LOCATIONS OF ALL HEADERS AND OR MASONRY LINTELS FOR INFILL WALLS.

3. WHERE ONE HOUR RATED WALL IS PERPENDICULAR TO ROOF TRUSSES, CLEARLY INDICATE HOW FIREWALL WILL BE CONTINUOUS FROM SLAB TO ROOF SHEATHING. NOTE: TRUSSES ARE NOT ALLOWED TO PENETRATE FIREWALL. ANY MODIFICATION OF TRUSSES WILL REQUIRE AN ENGINEERED DESIGN.

ELEVATIONS:

1. PROVIDE COMPLETE DRAWINGS OF ALL ELEVATIONS. INCLUDE PATIO COVERS, DECKS, FIREPLACES AND
BAY WINDOWS. SHOW BUILDING HEIGHTS.

2. NOTE AND SPECIFY ALL ROOF SLOPES

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A BUILDING CROSS-SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW
THE STRUCTURE IS BUILT.

2. NOTE AND SPECIFY ALL CONNECTIONS TO WOOD, FRAME OR MASONRY.

3. DETAIL AND NOTE ALL MASONRY WALL REINFORCEMENT PER R606.11.2.2.3.

4. CROSS-SECTIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLAN AND FRAMING PLANS.

PLUMBING PLANS:

1. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

2. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 -16 AND18- 24 2000 IRC.

2. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW. MISSING AT WATER HEATERS

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. NOTE THE LOCATION OF THE SERVICE PANEL. NOTE THE GROUNDING AND BONDING METHOD.

3. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE
DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

4. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1

5. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

6. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
12/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed