Permit Number - T03CM04938
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 1/7/2004 Building plans may not be reviewed and approved until copies of the stamped approved development, landscape, and NPPO plans are provided in each set of the building drawings. |
| 01/07/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/08/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/17/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/31/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/31/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide complete water and waste riser diagrams. Reference Section 103.2.3, UPC 1994. 2. Comment not addressed. Provide roof drain calculations and show how the roof is being protected with overflow drains (Sheet A7). Reference Appendix D, UPC 1994. 3. Termination of the excess pressure relief from the water heater over a service sink is not an approved location. Reference Section 608.5, UPC 1994. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/15/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 01/09/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |