Permit Number: T03CM04938
Parcel: Unknown

Address:
3085 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM04938
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2003 GERRY KOZIOL WWM REVIEW Approved
10/22/2003 JIM EGAN FIRE REVIEW Denied 1. One hour fire rated exit corridor required per 2000 IBC Sec. 1004.3.2.
2. Exit access door arrangement must comply with 2000 ibc Sec. 1004.2.2.1.
10/28/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum residual water pressure is 15 PSI. Revise the water pressure calculations and pipe sizing as required. Provide documentation of the minimum required operating pressure for the specified water closet. Reference Section 608.1, UPC 1994.
2. Revise the fixture unit calculations; the value for water fixture units assigned to a hose bibb in public service is 5 units, not 3 units. Reference Table 6-3, UPC 1994.
3. The tailpiece of a sink is not an approved termination for a condensate drain. Reference local amendments to Section 307.2.1, IMC 2000.
4. Provide complete water and waste riser diagrams. Reference Section 103.2.3, UPC 1994.
5. Provide roof drain calculations and show how the roof is being protected with overflow drains. Reference Appendix D, UPC 1994.
10/28/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide 1-hour separation for Storage Room 2. Reference Section 302.1.1, IBC, 2000.
2. Provide fire/smoke protection of ducts penetrating a rated corridor. Reference Section 715, IBC 2000.
3. Provide listing data for specified flexible duct.
10/28/2003 ROBERT SHERRY WATER REVIEW Approved
11/04/2003 Paul Machado ENGINEERING REVIEW Approved
11/13/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
11/13/2003
Building plans may not be reviewed and approved until copies of the approved development and landscape plans are included in the submittal package.
11/13/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Walls missing on plans. Complete drawings
2. Door swing on door at entry (101c) to be in direction of travel. References section 1003.3.1.2 IBC. Revise plans
3. Indicate location of required one-hour corridors and openings. Reference section 1004.3.2 IBC
4. Provide cross-section of one-hour fire partition to be utilized for corridors.
5. Include in door/window schedule requirements for openings in rated corridor.
6. Provide required water closet clearances per section 604.3.1 ANSI
7. Please co-ordinate calculations with plans. Sizes of members and designations differ.
11/14/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM04938 DENIED 11/14/03
1. Per our telephone conversation and followup voice-mail, WH size needs re-evaluation and revision.
2. Please add the following note in a conspicuous place: " All electrical work in patient care areas shall be done in accordance with NEC 517-13.
3. Per our telephone conversation, please re-calculate the demand loading for receptacles per NEC 220-13. This will modify feeder load calculations. Note that service load calculations over-stated continuous, and under-stated receptacle loads.
4. On Roof Plan, AHU-8 should be shown on Panel P2, not P3.
5. Please eliminate parallel paths to ground on line side of service disconnect. This effects runs 200 and 600. NEC 250-28 and 250-24 (b).

LAB 791.5550 X1106

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
11/18/2003 ANGIE SHOFFSTALL REJECT SHELF Completed