Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM04938
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/22/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. One hour fire rated exit corridor required per 2000 IBC Sec. 1004.3.2. 2. Exit access door arrangement must comply with 2000 ibc Sec. 1004.2.2.1. |
| 10/28/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum residual water pressure is 15 PSI. Revise the water pressure calculations and pipe sizing as required. Provide documentation of the minimum required operating pressure for the specified water closet. Reference Section 608.1, UPC 1994. 2. Revise the fixture unit calculations; the value for water fixture units assigned to a hose bibb in public service is 5 units, not 3 units. Reference Table 6-3, UPC 1994. 3. The tailpiece of a sink is not an approved termination for a condensate drain. Reference local amendments to Section 307.2.1, IMC 2000. 4. Provide complete water and waste riser diagrams. Reference Section 103.2.3, UPC 1994. 5. Provide roof drain calculations and show how the roof is being protected with overflow drains. Reference Appendix D, UPC 1994. |
| 10/28/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide 1-hour separation for Storage Room 2. Reference Section 302.1.1, IBC, 2000. 2. Provide fire/smoke protection of ducts penetrating a rated corridor. Reference Section 715, IBC 2000. 3. Provide listing data for specified flexible duct. |
| 10/28/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/04/2003 | Paul Machado | ENGINEERING | REVIEW | Approved | |
| 11/13/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 11/13/2003 Building plans may not be reviewed and approved until copies of the approved development and landscape plans are included in the submittal package. |
| 11/13/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Walls missing on plans. Complete drawings 2. Door swing on door at entry (101c) to be in direction of travel. References section 1003.3.1.2 IBC. Revise plans 3. Indicate location of required one-hour corridors and openings. Reference section 1004.3.2 IBC 4. Provide cross-section of one-hour fire partition to be utilized for corridors. 5. Include in door/window schedule requirements for openings in rated corridor. 6. Provide required water closet clearances per section 604.3.1 ANSI 7. Please co-ordinate calculations with plans. Sizes of members and designations differ. |
| 11/14/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM04938 DENIED 11/14/03 1. Per our telephone conversation and followup voice-mail, WH size needs re-evaluation and revision. 2. Please add the following note in a conspicuous place: " All electrical work in patient care areas shall be done in accordance with NEC 517-13. 3. Per our telephone conversation, please re-calculate the demand loading for receptacles per NEC 220-13. This will modify feeder load calculations. Note that service load calculations over-stated continuous, and under-stated receptacle loads. 4. On Roof Plan, AHU-8 should be shown on Panel P2, not P3. 5. Please eliminate parallel paths to ground on line side of service disconnect. This effects runs 200 and 600. NEC 250-28 and 250-24 (b). LAB 791.5550 X1106 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/18/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 11/18/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |