Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM04925
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04925
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2003 JIM EGAN FIRE REVIEW Approved
10/13/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/13/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
10/14/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The clothes washer in this application is not private but public. Revise plumbing fixture calculations accordingly.
2. Revise the pipe sizing as required to avoid exceeding the maximum velocity for copper piping. Reference Section A6.1, UPC 1994 and Section 610.0, IAPMO IS 3-93.
10/14/2003 ROBERT SHERRY WATER REVIEW Approved
10/14/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Relocate smoke detector from the supply duct to the return duct. Reference section 606.2.1, IMC 2000.
2. A splash block is not an approved termination point for the condensate drain and a roof drain may not be an approved termination point. Reference local amendments to Section 307.2.1, IMC 2000.
10/15/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE
10/16/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
10/23/2003 LLESNY1 WWM REVIEW Needs Review