Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/13/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
10/13/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/13/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
10/14/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The clothes washer in this application is not private but public. Revise plumbing fixture calculations accordingly. 2. Revise the pipe sizing as required to avoid exceeding the maximum velocity for copper piping. Reference Section A6.1, UPC 1994 and Section 610.0, IAPMO IS 3-93. |
10/14/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/14/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Relocate smoke detector from the supply duct to the return duct. Reference section 606.2.1, IMC 2000. 2. A splash block is not an approved termination point for the condensate drain and a roof drain may not be an approved termination point. Reference local amendments to Section 307.2.1, IMC 2000. |
10/15/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Z_DO NOT USE | |
10/16/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Z_DO NOT USE | |
10/23/2003 | LLESNY1 | WWM | REVIEW | Needs Review |