Permit Number: T03CM04924
Parcel: 140110360

Address:
5160 S TREAT AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04924
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied 1. DETAIL 4/S1 :
1. REINFORCEMENT OF JAMB REQUIRED TO EXTEND FROM SLAB INTO BOND BEAM ABOVE MASONRY OPENING. PROVIDE DETAIL FOR ANCHORAGE INTO SLAB AND INTO BOND BEAM.
2. LINTEL REINFORCING TO EXTEND 24" MINIMUM BEYOND MASONRY OPENING AT EACH SIDE,PROVIDE DETAIL.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
05/24/2004 ANGIE SHOFFSTALL REJECT SHELF Completed